Property: 152 Moverly Road, South Coogee NSW 2034 — Top (Northern) Townhouse Finding supported: G10 — Guest Suite ventilation + Guest Ensuite shower-recess overflow Source documents: Graphio CDC 3.00 / 4.00 / 5.00 / 6.00, Revision I, dated May 2023 Inspector: Dominic Ogburn · Access Property Services Visual Building Inspection: 23 April 2026
This appendix accompanies the consolidated building report and the defect summary for 152 Moverly Road. It supports finding G14 — Guest Suite ventilation. The calculation shows that the existing Guest Bedroom does not meet the natural-ventilation requirement of NCC 2022 HP Part H4D5 (deemed-to-satisfy path) and that a standard residential split-system air conditioner does not satisfy the AS 1668.2:2012 mechanical-ventilation alternative. Site-measurement of the Guest Bedroom floor area and of every operable element is still required before rectification is priced. The compliance position recorded below holds across the sensitivity range tested (12.6 – 18.2 m2), because the existing unobstructed openable area is approximately zero — well below 5% of the floor area at any plausible room dimension.
A.1 Floor area — basis of calculation
The Guest Bedroom dimensions have been read off Graphio CDC 3.00 / 4.00 / 5.00 / 6.00, Revision I, dated May 2023. The eastern external wall of the Guest Bedroom (RL 65.300, top townhouse) reads 5,010 mm centred on the room. The east-west width across the room body reads in the range 3,000 – 3,300 mm between the Ensuite wall and the eastern external wall.
For the calculation a 5.0 m × 3.0 m = 15.0 m2 floor area has been adopted. This is to be confirmed by tape on site as part of rectification scoping. Sensitivity at common alternative readings is shown in the table below — the compliance position is the same in every case.
| Floor dimensions | Floor area | Required openable area (5%) |
| 4.5 m × 2.8 m | 12.6 m2 | 0.63 m2 |
| 5.0 m × 3.0 m | 15.0 m2 | 0.75 m2 |
| 5.0 m × 3.5 m | 17.5 m2 | 0.88 m2 |
| 5.5 m × 3.3 m | 18.2 m2 | 0.91 m2 |
A.2 NCC HP Part H4D5 — natural ventilation (deemed-to-satisfy path)
NCC 2022 Volume Two, Housing Provisions, Part H4D5 requires a habitable room to be provided with natural ventilation via openings, doors or other devices opening directly to outside, with an aggregate unobstructed openable area of not less than 5% of the floor area of the room being ventilated.
For the adopted 15.0 m2 floor area, the required openable area is therefore 0.75 m2 (= 7,500 cm2).
Existing unobstructed openable area at time of inspection.
| Element | Type | Frame area | Unobstructed openable area |
| Main wall of glass | Fixed | n/a | 0 m2 |
| Louvre window | Operable in design — but cannot be opened at time of inspection | < 1.0 m2 | 0 m2 (effective) |
| Total | | | ≈ 0 m2 |
Compliance result: FAIL. The existing room provides effectively zero unobstructed openable area against a requirement of 0.75 m2.
The louvre cannot rescue compliance even if made operable. Only the open fraction of a louvre's frame counts as unobstructed openable area. A typical adjustable-blade louvre at full open delivers approximately 55% of its frame area as effective opening (product-specific; verify against datasheet). On that basis:
- Louvre frame 1.0 m2 × 0.55 = 0.55 m2 effective — still below the 0.75 m2 required
- To meet the 5% requirement using the louvre alone the frame would need to be approximately 1.4 m2 (e.g. 1,200 mm × 1,200 mm)
A.3 AS 1668.2:2012 — mechanical ventilation (performance alternative)
Where natural ventilation is not provided, NCC HP Part H4D5 permits a mechanical-ventilation system complying with AS 1668.2:2012 The use of ventilation and air-conditioning in buildings — Mechanical ventilation in buildings. AS 1668.2 mandates the introduction of outside air at a minimum rate, and the extraction of stale air, by a purpose-designed system.
Sizing for the Guest Bedroom (15.0 m2 floor area, design occupancy 2 persons):
| Method | Calculation | Outside-air rate |
| Per floor area (1.0 L/s/m2) | 1.0 × 15.0 | 15 L/s |
| Per occupant (5.0 L/s/person) | 5.0 × 2 | 10 L/s |
| Greater of the two — adopt | | 15 L/s |
That equates to 54 m3/h of continuous outside-air supply, or approximately 1.3 air changes per hour at a 2.7 m ceiling height (room volume ≈ 40.5 m3). At 5 L/s/person the indoor CO2 concentration is generally diluted to the 1,200 – 1,400 ppm range, consistent with the ABCB Indoor Air Quality Handbook guidance for residential bedrooms.
A.4 Why a residential split-system air conditioner does not satisfy AS 1668.2
A residential split-system air conditioner draws return air from the room, passes it across an evaporator coil for cooling or heating, and returns the same air to the room. It does not introduce outside air. Outside-air introduction at a split-system AC = 0 L/s.
AS 1668.2:2012 specifies the introduction of outside air at the rates set out in Table A1 (and equivalent sections) and the extraction of stale air by a purpose-designed mechanical system. A residential split AC does neither. It is therefore not a substitute for either:
- the 5% openable area required by NCC HP H4D5; or
- a compliant AS 1668.2 mechanical-ventilation installation.
Any submission that the Guest Bedroom is "ventilated by air conditioning" should be rejected on this basis.
A.5 Three rectification options — sized for 15 m2 Guest Bedroom
Each of the options below is engineered to deliver the compliance position required by H4D5 / AS 1668.2 for a 15.0 m2 floor area. Each is to be confirmed against the on-site tape measurement and against product-specific data before final pricing.
Option 1 — Operable and enlarged louvre window
- Required effective opening: 0.75 m2
- Typical adjustable-blade louvre delivers ~55% of frame area when fully open
- Required louvre frame: 0.75 ÷ 0.55 ≈ 1.4 m2
- Indicative size: 1,200 mm wide × 1,200 mm high = 1.44 m2 frame ✓
- Confirm louvre is fully operable, free from obstruction at full open, and weather-rated for the external location
- Re-render around the louvre frame to a level finish (also addresses the G14 render observation at p1140773)
Option 2 — Convert a section of the fixed glazing to an awning sash
- Awning-style sashes open more efficiently than louvres, typically 80 – 90% of frame area
- A 1,000 mm × 1,000 mm awning sash = 1.0 m2 frame delivers approximately 0.85 m2 effective opening ✓ (gives a margin above the 0.75 m2 requirement)
- Convert one panel of the existing fixed glazing rather than replacing the whole wall
- Verify glass is Grade A safety glazing per AS/NZS 2208:1996 / AS 1288:2021
- Verify thermal performance against the dwelling's BASIX commitment
Option 3 — AS 1668.2:2012 mechanical-ventilation system
- Continuous outside-air supply: ≥ 15 L/s
- Typical small ducted mechanical ventilation with heat recovery (MVHR) unit sized at 15 – 30 L/s; suit the supply to Guest Bedroom and stale-air extract from the Guest Ensuite (which would also assist the AS 3740 wet-area extract requirement)
- Installation to be designed and certified by a registered HVAC engineer working to AS 1668.2:2012; commissioning report and AS 1668.2 compliance certificate to be retained
- This is a commercial-grade installation, not a residential split AC — explicit on this point because it is the most common misunderstanding in this category
A.6 Limits of this calculation
This appendix is honest about the limits of what it can establish from drawings and photographs alone:
- The 15 m2 floor area is a plan-derived estimate. Confirm by tape on site before any rectification is priced. The compliance position holds across the 12.6 – 18.2 m2 sensitivity range.
- The louvre effective-opening ratio of 55% is a typical figure for adjustable-blade external louvres at full open. Some high-performance products achieve 70%+. Use the manufacturer's certified open-area figure when sizing.
- The AS 1668.2 outside-air rate has been calculated using both the per-floor-area and per-occupant methods, taking the greater. A registered HVAC engineer will use the actual product specifications and AS 1668.2 Table A1 directly.
- Rectification options are indicative sizings to demonstrate the order of magnitude required. Final design (sash type, glass specification, mechanical equipment selection) is to be by the relevant licensed designer / engineer.
Standards cited in this appendix
- NCC 2022 Volume Two, Housing Provisions Part H4D5 — Natural ventilation (5% openable-area rule)
- NCC 2022 Volume Two, Housing Provisions Part H4D6 — Ventilation through adjoining rooms
- AS 1668.2:2012 — The use of ventilation and air-conditioning in buildings — Mechanical ventilation in buildings (outside-air rates, Table A1)
- AS/NZS 2208:1996 — Safety glazing materials in buildings
- AS 1288:2021 — Glass in buildings — selection and installation
- AS 3740:2021 — Waterproofing of domestic wet areas (referenced for the related Guest Ensuite shower-recess finding under G14)
- ABCB Indoor Air Quality Handbook (current version) — guidance on residential ventilation rates and CO2 dilution
— End of Appendix A —